10KVA Backup Power System With AVR
CP Series 3/1 phase online UPS low frequency double conversion with intelligent digitization:
energy saving,high precision, digitization and hommization
Capacity for single machine from 10KVA-40KVA:
Stable performance for advanced digital circuit system.Intelligent battery charger,durable and worry-saving.Whole course guardianship for intelligent detection system.Smart communication interface RS232 and remoted monitoring SNMP.The sixth generation IGBT and high-speed static switch shift technology.Direct LCD data display and LED work status display,without difficulties between machnine and human.Machine principle:
The UPS is a multiple proctective uninterruptible power system,with output isolation transformer,double convertion and digitization function.When AC is normal,it will filter the interruption from AC, and change AC rectifier into pure DC firstly, then change DC into pure sine wave AC output by inverter.At the mean time,the battery will be charged.When AC is abnormal,the DC stored by battery will invert to AC to output,guaranteeing the loads can get the high quality power electricity;It will shift to bypass automatically to supply power while the inverter is off or have faults.
Principle chart:
Technical parameter for CP Series
Model | CP10KVA3/1 |
Nominal capacity(W) | 8000W |
Work mode | Low frequency on line |
Number of phase | Three phase in one phase out (N+G) |
Nominal input voltage | 380VAC |
Range | ±25% |
Nominal input frequency | 50HZ ±10% |
Output voltage | 220VAC±1% |
Output frequency | 50HZ±0.5%(unlocked) |
Transient response | ±4%(100%load) |
wave form | Sine wave THD<3% |
overload capacity | 120-125%for 60 seconds,go to bypass when the load is more than 150% |
Crest factor | 3:1 |
Battery type | sealed maintenance-free lead-acid battery |
DC voltage | 192V(16*12V battery) |
Charge current | 1-5A (adjustable) |
Charge mode | constant current first then constant voltage,automatically covert to float |
Floating charge voltage | 220V |
Efficiency | ≥90% |
Tranfer time | 0 for AC fault, <2ms for by pass |
Protection | input over-current,break automatically;overload,overheat;bypass |
EMI radiation | 40dB for 10-100KHZ, 70db for 100KHZ-100MHZ |
Auto alarm utility failure | alarm 4seconds/time,keeping 90 seconds |
Low battery | alarm 1 time/second(auto shutdown&restart) |
Overload | continuous buzzer for 60 second then bypass |
Fault | continuous buzzer |
LED display | AC input/bypass/inverter/low battery voltage/overload/fault |
LCD display | UPS status/input/output/DC voltage/output frequency/load percentage |
Interface | RS232; remoted monitoring SNMP (optional); dry contact interface (optional) |
Ambient temperature | 0-40°C |
Humidity | 20-90%(non-condensing) |
Noise | <58dB (with 1 meter distance) |
Enclosure dimension (mm) L*W*H | 480*340*825
|
Package dimension (mm) L*W*H | 625*400*1000 |
package material | wood |
G.W.(excluding battery) | 136KG |